Inspection report

12 Oak St, Dothan AL 36301

Inspected 2026-8-27 · by Ben Morehead · for Dana Whitfield

Summary

The short version of this report. Every safety item is listed here; the rest live in their sections.

  • The report flags several safety items throughout the home, including concerns at the electrical panels, the water heater wiring, and life-safety alarms. These are detailed in the safety list directly below.
  • The roof system needs attention on multiple fronts: shingles are near the end of their service life, flashings at the chimney base are substandard, and a missing cricket allows debris to accumulate. The attic adds to this picture, with a cut or damaged roof truss noted and insulation well below current standards.
  • The electrical panels A and C each have conditions that a qualified electrician should evaluate, including open slots, missing knockouts, an incomplete circuit legend, and GFCI and AFCI protection gaps in the kitchen and bathrooms.
  • The water heater is at or beyond its expected service life and could not be fully evaluated because the safety switch was off. Exposed and spliced wiring at the water heater also needs correction.
  • Windows throughout the home show a pattern of failed seals, cracked glass, and difficulty operating, and several exterior openings have caulk or weatherstripping gaps that can let in water and reduce energy efficiency.

The plumbing supply, drain, and waste lines all appeared serviceable, and the heat pump system, installed in 2026, operated properly with serviceable filters, ducts, and controls.

Safety items 15

  1. Cracks, holes, settlement, heaving and/or deterioration resulting in trip hazards were found in the driveway.Grounds
  2. The range could tip forward.Kitchen
  3. Splices in service conductors at the service mast head were exposed.Electric
  4. One or more slots where circuit breakers are normally installed were open in panel(s) #C.Electric
  5. One or more knockouts were missing from panel(s) #A.Electric
  6. One or more screws used to secure the cover or dead front to panel(s) #C had sharply pointed tips or were too long.Electric
  7. One or more ground fault circuit interrupter (GFCI) devices protecting receptacles at the bathroom(s) wouldn't reset when tripped.Electric
  8. One or more electric receptacles at the kitchen and/or laundry area had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present.Electric
  9. One or more electrical receptacles had no visible arc-fault circuit interrupter (AFCI) protection, or the inspector was unable to determine whether AFCI protection was present.Electric
  10. Based on the age of this structure and the appearance of existing smoke alarms, the alarms may have been installed more than 10 years ago.Electric
  11. Smoke alarms were missing from one or more bedrooms.Electric
  12. Carbon monoxide alarms were missing Hallway leading to bedrooms.Electric
  13. Wiring for the water heater's power supply was exposed and subject to damage.Water Heater
  14. Wiring for the water heater's power supply was substandard, with exposed splices.Water Heater
  15. One or more solid fuel-burning fireplaces or stoves were found at the property.Fireplaces, Stoves, Chimneys and Flues

33 more findings in the report: 15 repair or replace, 8 repair or maintain, 2 minor defects, 5 to evaluate, 3 maintenance items. Each one sits in its section below, in the inspector's order.

General Information

Report number
DEMO
Time started
8:00
Time finished
10:30
Client present for discussion at end of inspection
No
Inspection fee
450
Payment method
Credit card
Buildings inspected
One house
Number of residential units inspected
1
Age of main building
1979
Source for main building age
Realtor
Occupied
No

Building Code Disclaimer — Jurisdictional Variance

Our inspections are based on best practices and standard building practices across the industry. These practices typically align with the most current building codes; however, building codes are revised on a regular cycle, with an updated version published approximately every three years.

In Alabama, if a jurisdiction has not adopted a designated building code, that area defaults to the state-adopted code, which is currently the 2021 IRC.

It is important to understand that, regardless of the most current code edition available, municipalities, counties, and states can individually choose which code edition — and which specific provisions within that edition — to adopt and enforce within their jurisdiction. As a result, one jurisdiction may be enforcing the 2021 code while a neighboring jurisdiction may still be operating under a much older version, such as 2009.

Cornerstone Home Inspectors performs inspections across numerous jurisdictions and multiple states, and it is not practical to track the specific code edition and amendments adopted by every individual municipality. Should any question arise between the buyer, seller, or contractor regarding the applicability of a specific code reference in this report, we recommend contacting the local Authority Having Jurisdiction (AHJ) or, where applicable, the manufacturer of the product in question for clarification.

General Recommendation Disclaimer — Qualified Persons

Any recommendations made throughout this report for further evaluation, repair, or replacement should be performed by a licensed contractor, tradesperson, or other qualified professional with expertise in the relevant field. This applies regardless of whether "licensed," "qualified," or a specific trade is stated for an individual finding.

Weather

Grounds

Limitations. Unless specifically included in the inspection, the following items and any related equipment, controls, electric systems and/or plumbing systems are excluded from this inspection: detached buildings or structures; fences and gates; retaining walls; underground drainage systems, catch basins or concealed sump pumps; swimming pools and related safety equipment, spas, hot tubs or saunas; whether deck, balcony and/or stair membranes are watertight; trees, landscaping, properties of soil, soil stability, erosion and erosion control; ponds, water features, irrigation or yard sprinkler systems; sport courts, playground, recreation or leisure equipment; areas below the exterior structures with less than 3 feet of vertical clearance; invisible fencing; sea walls, docks and boathouses; retractable awnings. Any comments made regarding these items are as a courtesy only.

Condition of fences and gates
Appeared serviceable
Fence and gate material
Wood
Site profile
Level
Condition of driveway
Appeared serviceable
Driveway material
Poured in place concrete
Condition of sidewalks and/or patios
Appeared serviceable
Sidewalk material
Poured in place concrete

Minor deterioration (e.g. cracks, holes, settlement, heaving) was found in the driveway. The client may wish to have repairs made for cosmetic reasons.

SafetyRepair/Maintain

Cracks, holes, settlement, heaving and/or deterioration resulting in trip hazards were found in the driveway. For safety reasons, recommend that a qualified contractor repair as necessary.

Minor deterioration (e.g. cracks, holes, settlement, heaving) was found in sidewalks or patios. The client may wish to have repairs made for cosmetic reasons.

Exterior Photos of the house and surrounding area. - For Information Only

Exterior and Foundation

Limitations. The inspector performs a visual inspection of accessible components or systems at the exterior. Items excluded from this inspection include below-grade foundation walls and footings; foundations, exterior surfaces or components obscured by vegetation, stored items or debris; wall structures obscured by coverings such as siding or trim. Some items such as siding, trim, soffits, vents and windows are often high off the ground, and may be viewed using binoculars from the ground or from a ladder. This may limit a full evaluation. Regarding foundations, some amount of cracking is normal in concrete slabs and foundation walls due to shrinkage and drying. Note that the inspector does not determine the adequacy of seismic reinforcement.

Wall inspection method
Viewed from ground, from a ladder
Condition of wall exterior covering
Required repair, replacement and/or evaluation (see comments below)
Apparent wall structure
Wood frame
Wall covering
Vinyl, Brick veneer, Metal
Condition of foundation and footings
Appeared serviceable
Apparent foundation type
Concrete slab on grade
Foundation/stem wall material
Concrete slab on grade
Footing material (under foundation stem wall)
Poured in place concrete, Concrete slab
Repair/Replace

Some sections of siding and/or trim were substandard. Recommend that a qualified person repair, replace or install siding or trim as necessary.

Maintain

Caulk was missing and/or deteriorated in some areas. For example, around windows and/or at siding butt joints. Recommend that a qualified person renew or install caulk as necessary. Where gaps are wider than 1/4 inch, an appropriate material other than caulk should be used. For more information, visit:
http://www.reporthost.com/?CAULK

Repair/Replace

Flashing at one or more locations was missing and/or substandard. Leaks can occur as a result. Recommend that a qualified person repair, replace or install flashing as necessary, and per standard building practices.

Gap is larger than a quarter inch which caulking is not recommended in gaps that large. Flashing needs to be used.

Roof

Limitations. The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; solar roofing components. Any comments made regarding these items are made as a courtesy only. Note that the inspector does not provide an estimate of remaining life on the roof surface material, nor guarantee that leaks have not occurred in the roof surface, skylights or roof penetrations in the past. Regarding roof leaks, only active leaks, visible evidence of possible sources of leaks, and evidence of past leaks observed during the inspection are reported on as part of this inspection. The inspector does not guarantee or warrant that leaks will not occur in the future. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high wind and rain, melting snow) would be needed to do so. Occupants should monitor the condition of roofing materials in the future. For older roofs, recommend that a professional inspect the roof surface, flashings, appurtenances, etc. annually and maintain/repair as might be required. If needed, the roofer should enter attic space(s). Regarding the roof drainage system, unless the inspection was conducted during and after prolonged periods of heavy rain, the inspector was unable to determine if gutters, downspouts and extensions perform adequately or are leak-free.

Roof inspection method
Partially traversed
Condition of roof surface material
Required repair, replacement and/or evaluation (see comments below)
Roof surface material
Asphalt or fiberglass composition shingles
Roof type
Gable, Flat or low slope
Apparent number of layers of roof surface material
One
Condition of exposed flashings
Required repair, replacement and/or evaluation (see comments below)
Condition of gutters, downspouts and extensions
None
Gutter and downspout installation
None
EvaluateConcern

The roof surface appeared to be near the end of its service life and will likely need replacing in the near future even if repairs are made now. Recommend discussing replacement options with a qualified contractor, and budgeting for a replacement roof surface in the near future.

Repair/ReplaceMonitor

One or more chimneys were wider than 30" or had no cricket installed above. A cricket is a peaked saddle behind the chimney that diverts water around the sides of the chimney. Without a cricket, debris such as leaves, needles or moss is likely to accumulate above the chimney, and can cause leaks. At a minimum, monitor this area and its flashings for accumulated debris, and clean debris as necessary. Recommend that a qualified contractor install a cricket per standard building practices.

Repair/Maintain

One or more roofing nails or staples were loose, resulting in holes in shingles, loose shingles or lifting shingles. Leaks may occur and can be a conducive condition for wood-destroying organisms. Recommend that a qualified contractor repair as necessary.

Repair/Replace

Some composition shingles were cracked and/or loose. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor repair as necessary. For example, by replacing shingles.

Repair/Maintain

One or more roof flashings were lifting. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person repair as necessary.

Repair/ReplaceEvaluate

Flashings at the base of one or more chimneys were substandard. Leaks can occur as a result. This is a conducive condition for wood-destroying organisms. Recommend that a qualified contractor evaluate and repair as necessary.

Minor Defect

None/partial roof drainage system was installed. Rainwater may come in contact with the building exterior or accumulate around the building foundation as a result. This can be a conducive condition for wood-destroying organisms. Recommend that a qualified contractor install roof drainage components where missing per standard building practices.

Attic and Roof Structure

Limitations. The following items or areas are not included in this inspection: areas that could not be traversed or viewed clearly due to lack of access; areas and components obscured by insulation. Any comments made regarding these items are made as a courtesy only. The inspector does not determine the adequacy of the attic ventilation system. Complete access to all roof and attic spaces during all seasons and during prolonged periods of all types of weather conditions (e.g. high/low temperatures, high/low humidity, high wind and rain, melting snow) would be needed to do so. The inspector is not a licensed engineer and does not determine the adequacy of roof structure components such as trusses, rafters or ceiling beams, or their spacing or sizing.

Attic inspection method
Partially traversed
Location of attic access point #A
Hallway
Attic access points that were opened and viewed, traversed or partially traversed
A
Condition of roof structure
Required repair, replacement and/or evaluation (see comments below)
Roof structure type
Rafters
Ceiling structure
Ceiling joists
Condition of insulation in attic (ceiling, skylight chase, etc.)
Required repair, replacement and/or evaluation (see comments below)
Ceiling insulation material
Fiberglass roll or batt
Approximate attic insulation R value (may vary in areas)
R-19
Vermiculite insulation present
None visible
Vapor retarder
Installed
Condition of roof ventilation
Required repair, replacement and/or evaluation (see comments below)
Roof ventilation type
Ridge vent(s), Enclosed soffit vents
Exhaust ducts
Terminates in attic or soffit
Repair/ReplaceEvaluate

Observation: One or more roof trusses were observed to be cut, damaged, or modified. The roof structure has likely been weakened as a result. Trusses are engineered components and should not be cut, drilled, notched, or otherwise modified by builders or homeowners without engineering review.

Code Reference: IRC R802.10.4 (truss design drawings/bracing; alterations require engineering approval)

Recommendation: Recommend evaluation by a licensed structural engineer to assess the extent of damage and prescribe repairs — which may involve restoring the truss to its original configuration or an approved alternative reinforcement method. A qualified contractor should perform repairs strictly per the engineer's specifications.

Truss was modified to install the HVAC unit. Bracing and boards were installed.

EvaluateMonitor

What appeared to be past water stains were visible on the roof structure at one or more locations in the attic. However, no elevated levels of moisture were found at these stains during the inspection. The stains may have been caused by a past leak. Recommend asking the property owner about past leaks. Monitor these areas in the future, especially after heavy rains to determine if active leaks exist. If leaks are found, recommend that a qualified contractor evaluate and repair as necessary.

Repair/Replace

The ceiling insulation installed in the attic was substandard and appeared to have an R rating that's significantly less than current standards (R-38). Heating and cooling costs will likely be higher due to poor energy efficiency. Recommend that a qualified contractor install insulation for better energy efficiency and per standard building practices.

Repair/Replace

One or more exhaust fan ducts in the attic were not attached to a vent hood or cap. As a result, conditioned air will enter the attic when the fan is operated. Ducts terminating near an attic vent but without a dedicated vent hood or cap will likely blow conditioned air back into the attic. This can result in excessive moisture in the attic. Recommend that a qualified contractor repair per standard building practices, so exhaust fan ducts are permanently fastened to vent hoods or caps.

Additional Pictures of the Attic - For Information Only

Kitchen

Limitations. The following items are not included in this inspection: household appliances such as stoves, ovens, cook tops, ranges, warming ovens, griddles, broilers, dishwashers, trash compactors, refrigerators, freezers, ice makers, hot water dispensers and water filters; appliance timers, clocks, cook functions, self and/or continuous cleaning operations, thermostat or temperature control accuracy, and lights. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of the remaining life of appliances, and does not determine the adequacy of operation of appliances. The inspector does not note appliance manufacturers, models or serial numbers and does not determine if appliances are subject to recalls. Areas and components behind and obscured by appliances are inaccessible and excluded from this inspection.

Condition of counters
Required repair, replacement and/or evaluation (see comments below)
GFCI protection
Not present
Condition of cabinets
Appeared serviceable
Condition of sinks and related plumbing
Appeared serviceable
Condition of under-sink food disposal
N/A (none installed)
Condition of dishwasher
Required repair, replacement and/or evaluation (see comments below)
Condition of ranges, cooktops and/or ovens
Appeared serviceable
Range, cooktop, oven type
Electric
Anti-tip bracket
Not present
Type of ventilation
Hood or built into microwave over range or cooktop
Condition of refrigerator
Appeared serviceable
Condition of built-in microwave oven
N/A (none installed)
Condition of hot water dispenser
N/A (none installed)
Condition of trash compactor
N/A (none installed)

For Information Only

Minor Defect

Countertops and/or backsplashes were damaged or deteriorated. Recommend repairing or replacing as necessary.

Repair/ReplaceEvaluate

The inspector was unable to determine if the dishwasher's drain line had a high loop or air gap (e.g. drain line not visible). A high loop is created by routing the drain line up to the bottom surface of the counter top above and securely fastening it to that surface. An air gap is a device that makes the drain line non-continuous. Both of these prevent waste-water backflow from entering the dishwasher, and possibly flooding out of the dishwasher if/when a siphon occurs. Some newer dishwashers have these devices built in. Recommend reviewing the dishwasher's installation instructions, consulting with the property owner and/or having a qualified contractor evaluate further to determine if a high loop and air gap are installed or needed. If not installed, and none is built into the dishwasher, then recommend that a qualified contractor install a high loop and air gap per standard building practices.

SafetyRepair/Replace

The range could tip forward. An anti-tip bracket may not be installed. This is a potential safety hazard since the range can tip forward when weight is applied to the open door, such as when a small child climbs on it or if heavy objects are dropped on it. Anti-tip brackets have been sold with all free-standing ranges since 1985. Recommend installing an anti-tip bracket to eliminate this safety hazard. For more information, visit:
http://www.reporthost.com/?ATB

The anti-tip devices come with the units and does not appear to be in the lower drawer.

Electric

Limitations. The following items are not included in this inspection: generator systems, transfer switches, surge suppressors, inaccessible or concealed wiring; underground utilities and systems; low-voltage lighting or lighting on timers or sensors. Any comments made regarding these items are for courtesy only. Note that the inspector does not determine the adequacy of grounding or bonding, if this system has an adequate capacity for the client's specific or anticipated needs, or if this system has any reserve capacity for additions or expansion. The inspector does not operate circuit breakers as part of the inspection and does not install or change light bulbs. The inspector does not evaluate every wall switch or receptacle, but instead tests a representative number of them per various standards of practice. When furnishings, stored items, or child-protective caps are present, some receptacles are usually inaccessible and are not tested; these are excluded from this inspection. Receptacles that are not of standard 110-volt configuration, including 240-volt dryer receptacles, are not tested and are excluded. The functionality of, power source for, and placement of smoke and carbon monoxide alarms are not determined as part of this inspection. Upon taking occupancy, proper operation and placement of smoke and carbon monoxide alarms should be verified, and batteries should be changed. These devices have a limited lifespan and should be replaced every 10 years. The inspector attempts to locate and evaluate all main and sub-panels. However, panels are often concealed. If panels are found after the inspection, a qualified electrician should evaluate and repair them if necessary. The inspector attempts to determine the overall electrical service size, but such estimates are not guaranteed, as the overall capacity may be diminished by lower-rated components in the system. A licensed electrician should make any recommended repair.

Electric service condition
Required repair, replacement and/or evaluation (see comments below)
Primary service type
Overhead
Number of service conductors
3
Service voltage (volts)
120-240
Estimated service amperage
200
Primary service overload protection type
Circuit breakers
Service entrance conductor material
Stranded aluminum
Main disconnect rating (amps)
Not applicable, no single main disconnect
System ground
Ground rod(s) in soil
Condition of main service panel
Required repair, replacement and/or evaluation (see comments below)
Condition of sub-panel(s)
Required repair, replacement and/or evaluation (see comments below)
Location of main service panel #A
Building exterior
Location of sub-panel #C
Laundry room
Location of main disconnect
No single main disconnect, use all breakers in main service panel, At main disconnect panel outside
Condition of branch circuit wiring
Required repair, replacement and/or evaluation (see comments below)
Branch circuit wiring type
non-metallic sheathed, copper, Aluminum multi-strand
Solid strand aluminum branch circuit wiring present
None visible
Ground fault circuit interrupter (GFCI) protection present
Yes
Arc fault circuit interrupter (AFCI) protection present
No
Smoke alarms installed
Yes, but not tested
Carbon monoxide alarms installed
No, recommend install
Smoke alarm power source(s)
Battery
SafetyRepair/Replace

Splices in service conductors at the service mast head were exposed. Splices should be covered with plastic insulators or tape to prevent exposed, energized wires. This is a potential shock hazard. Recommend that a qualified electrician repair per standard building practices.

Local electrical provider typically will wrap for no charge.

Repair/Replace

The inspector was unable to open and evaluate panel(s) #C because paint, caulk or wallpaper would be damaged. The condition of these panel(s) is unknown and they are excluded from this inspection. Repairs may be needed. Recommend that a qualified person correct conditions, or that a qualified contractor make repairs if necessary so panels can be opened, and that a qualified person fully evaluate panel(s).

Repair/MaintainEvaluate

The legend for circuit breakers or fuses in panel(s) #A and C was missing, incomplete, illegible or confusing. This is a potential shock or fire hazard in the event of an emergency when power needs to be turned off. Recommend correcting the legend so it's accurate, complete and legible. Evaluation by a qualified electrician may be necessary.

SafetyRepair/Maintain

One or more slots where circuit breakers are normally installed were open in panel(s) #C. Energized equipment was exposed and is a shock hazard. Recommend that a qualified person install closure covers where missing.

SafetyRepair/Maintain

One or more knockouts were missing from panel(s) #A. Holes in panels are a potential fire hazard if a malfunction ever occurs inside the panel. Rodents can also enter panels through holes. Recommend that a qualified person install knockout covers where missing and per standard building practices.

Evaluate

One or more circuit breakers in panel(s) #A were in the off position. Consult with the property owner to determine why breakers were tripped or off, and that a qualified electrician evaluate and repair if necessary. Note that the inspector does not operate circuit breakers.

SafetyMinor Defect

One or more screws used to secure the cover or dead front to panel(s) #C had sharply pointed tips or were too long. Energized wires can be damaged by such screws. This is a potential shock hazard, especially when screws are being removed or installed. Recommend that a qualified person replace such screws with screws that are approved for this purpose (e.g. blunt-tip screws of the correct length). Because energized wires may be in contact with these screws, the client should consider having a qualified electrician replace the screws.

Main Panel #A Photos

Subpanel #C Photos

SafetyRepair/ReplaceEvaluate

One or more ground fault circuit interrupter (GFCI) devices protecting receptacles at the bathroom(s) wouldn't reset when tripped. This is a potential shock hazard. Recommend that a qualified electrician evaluate and repair as necessary.

GFCI never tested as it was already in the trip position at the time of the inspection and would not reset.

SafetyRepair/ReplaceEvaluate

One or more electric receptacles at the kitchen and/or laundry area had no visible ground fault circuit interrupter (GFCI) protection, or the inspector was unable to determine if GFCI protection was present. If not GFCI-protected, receptacles in wet areas pose a shock hazard. Recommend that a qualified electrician evaluate and install GFCI protection if necessary and per standard building practices. General guidelines for GFCI-protected receptacles include the following locations:
[list]
[*]Outdoors (since 1973) [/*]
[*]Bathrooms (since 1975) [/*]
[*]Garages (since 1978) [/*]
[*]Kitchens (since 1987) [/*]
[*] Crawl spaces and unfinished basements (since 1990) [/*]
[*]Wet bar sinks (since 1993) [/*]
[*]Laundry and utility sinks (since 2017) [/*]
[/list]
For more information, visit:
http://www.reporthost.com/?GFCI

SafetyRepair/ReplaceEvaluate

One or more electrical receptacles had no visible arc-fault circuit interrupter (AFCI) protection, or the inspector was unable to determine whether AFCI protection was present. This is a potential safety hazard. It is recommended that a qualified electrician evaluate the circuits in question and install AFCI protection where necessary and consistent with standard building practices.
Disclaimer: AFCI protection was not required by code prior to 1999. Because AFCI protection is widely recognized as a safety improvement, homeowners may wish to consider upgrading older, unprotected circuits even where not legally required.
General guidelines for AFCI-protected receptacle locations are noted below.

Important: Not all municipalities or jurisdictions enforce these code requirements equally. To determine the specific requirements in your area, you must contact the local jurisdiction of authority.

The 2021 IRC significantly expanded the locations where AFCI protection is required compared to previous editions. AFCI protection is now required for virtually all 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets (receptacles, lighting, etc.) in the following areas of one- and two-family dwellings and townhouses:
Required AFCI Locations (2021 IRC):

Bedrooms (required since 1999; still required)
Closets (new in 2021)
Hallways (new in 2021)
Laundry areas (new in 2021)
Kitchens (new in 2021 — the most significant change; nearly all kitchen circuits now require AFCI)
Family rooms, dining rooms, living rooms, parlors, libraries, dens, sunrooms, recreation rooms, and similar rooms (essentially all living areas)
All remaining habitable areas not specifically exempted

Key Exceptions (AFCI still NOT required under the 2021 IRC):

Bathrooms
Garages
Outdoors
Crawl spaces and unfinished basements
Circuits supplying only hard-wired smoke/CO alarms (if on a dedicated circuit)
Branch circuits supplying only permanently connected appliances that are not easily moved (e.g., a dedicated furnace or water heater circuit)

Evaluate

Bulbs in one or more light fixtures were missing or broken. These light fixtures couldn't be fully evaluated. If replacement bulbs are inoperable, then recommend that a qualified electrician evaluate and repair or replace light fixtures as necessary.

Repair/Maintain

The front door's doorbell appeared to be inoperable. Recommend that a qualified person repair as necessary.

SafetyRepair/Maintain

Based on the age of this structure and the appearance of existing smoke alarms, the alarms may have been installed more than 10 years ago. According to [url="http://www.nfpa.org"]National Fire Protection Association[/url], aging smoke alarms don't operate as efficiently and often are the source for nuisance alarms. Older smoke alarms are estimated to have a 30% probability of failure within the first 10 years. Newer smoke alarms do better, but should be replaced after 10 years. Unless you know that the smoke alarms are new, replacing them when moving into a new residence is also recommended by NFPA. For more information, visit:
http://www.reporthost.com/?SMKALRMLS

SafetyRepair/Replace

Smoke alarms were missing from one or more bedrooms. Smoke alarms should be installed as necessary so a functioning alarm exists in each hallway leading to bedrooms, in each bedroom and on each level. For more information, visit:
http://www.reporthost.com/?SMKALRM

SafetyRepair/Maintain

Carbon monoxide alarms were missing Hallway leading to bedrooms. This is a potential safety hazard. Some states and/or municipalities require CO alarms to be installed in the vicinity of each sleeping area, on each level and in accordance with the manufacturer's recommendations. Recommend installing additional carbon monoxide alarms per these standards. For more information, visit:
http://www.reporthost.com/?COALRM

Plumbing / Fuel Systems

Limitations. The following items are not included in this inspection: private/shared wells and related equipment; private sewage disposal systems; hot tubs or spas; main, side and lateral sewer lines; gray water systems; pressure boosting systems; trap primers; incinerating or composting toilets; fire suppression systems; water softeners, conditioners or filtering systems; plumbing components concealed within the foundation or building structure, or in inaccessible areas such as below tubs; underground utilities and systems; overflow drains for tubs and sinks; backflow prevention devices. Any comments made regarding these items are as a courtesy only. Note that the inspector does not operate water supply or shut-off valves due to the possibility of valves leaking or breaking when operated. The inspector does not test for lead in the water supply, the water pipes or solder, does not determine if plumbing and fuel lines are adequately sized, and does not determine the existence or condition of underground or above-ground fuel tanks.

Condition of service and main line
Appeared serviceable
Water service
Public
Location of main water meter
By street
Location of main water shut-off
Building exterior
Service pipe material
Plastic
Condition of supply lines
Appeared serviceable
Supply pipe material
Copper
Condition of drain pipes
Appeared serviceable
Drain pipe material
Plastic
Condition of waste lines
Appeared serviceable
Waste pipe material
Plastic
Location(s) of plumbing clean-outs
Building exterior
Vent pipe condition
Appeared serviceable
Vent pipe material
Plastic
Sump pump installed
None visible
Sewage ejector pump installed
None visible

Meter & Main Shut-Off - For Information Only

Repair/Maintain

One or more waste line clean-out caps were missing, damaged or substandard. Leaks can occur or sewer gases can enter living spaces as a result. Recommend that a qualified plumber replace the cap(s) as necessary.

Water Heater

Limitations. Evaluation of and determining the adequacy or completeness of the following items are not included in this inspection: water recirculation pumps; solar water heating systems; Energy Smart or energy saver controls; catch pan drains. Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on water heaters, does not determine if water heaters are appropriately sized, or perform any evaluations that require a pilot light to be lit or a shut-off valve to be operated.

Condition of water heater
Required repair, replacement and/or evaluation (see comments below), Near, at or beyond service life
Type
Tank
Energy source
Electricity
Estimated age
2011
Capacity (in gallons)
38
Temperature-pressure relief valve installed
Yes
Manufacturer
Rheem
Model number
82SV40-2
Serial number
RH 0611205982
Location of water heater
Laundry room
Hot water temperature tested
Yes
Evaluate

The water heater's safety switch was off. The water heater and hot water supply system (e.g. faucets, controls) were not fully evaluated because of this. Recommend that a full evaluation be made by a qualified person when conditions have been corrected so the water heater is operable. Note that per the standards of practice for various professional home inspection organizations, the inspector does not operate shut-off valves, pilot lights or over-current protection devices, or any controls other than "normal controls."

The estimated useful life for most water heaters is generally cited as 10–14 years, depending on fuel type, water quality, and maintenance history. This water heater appeared to be at this age and/or its useful lifespan and may need replacing at any time. Recommend budgeting for a replacement in the near future, or considering replacement now before any leaks occur. The client should be aware that significant flooding can occur if the water heater fails. If not replaced now, consider having a qualified person install a catch pan and drain or a water alarm to help prevent damage if water does leak.

Based on the capacity of the water heater, the number of bedrooms in this structure and the number of occupants expected to live in this structure, this water heater may be undersized. Consult with a qualified plumber or water heater distributor for more information, and may wish to upgrade the size of the water heater.

A water heater was installed in or over a finished living space or in an area where leaking can cause damage, and no catch pan or drain was installed. Catch pans and drains prevent water damage to finished interior spaces below if or when the water heater leaks or is drained. If concerned, consult with a qualified contractor about installing these. Note that drain lines for catch pans are usually installed below the floor level and are difficult at best to install in an existing home.

SafetyRepair/Replace

Wiring for the water heater's power supply was exposed and subject to damage. Standard building practices call for non-metallic sheathed wiring to be protected with BX armored conduit to prevent damage. This is a potential safety hazard for shock. Recommend that a qualified contractor repair per standard building practices.

SafetyRepair/Replace

Wiring for the water heater's power supply was substandard, with exposed splices. This is a potential safety hazard for shock or fire. Recommend that a qualified person repair per standard building practices.

Heating, Ventilation and Air Condition (HVAC)

Limitations. The following items are not included in this inspection: humidifiers, dehumidifiers, electronic air filters; solar, coal or wood-fired heat systems; thermostat or temperature control accuracy and timed functions; heating components concealed within the building structure or in inaccessible areas; underground utilities and systems; safety devices and controls (due to automatic operation). Any comments made regarding these items are as a courtesy only. Note that the inspector does not provide an estimate of remaining life on heating or cooling system components, does not determine if heating or cooling systems are appropriately sized, does not test coolant pressure, or perform any evaluations that require a pilot light to be lit, a shut-off valve to be operated, a circuit breaker to be turned "on" or a serviceman's or oil emergency switch to be operated. It is beyond the scope of this inspection to determine if furnace heat exchangers are intact and free of leaks. Condensation pans and drain lines may clog or leak at any time and should be monitored while in operation in the future. Where buildings contain furnishings or stored items, the inspector may not be able to verify that a heat source is present in all "liveable" rooms (e.g. bedrooms, kitchens and living/dining rooms).

General heating system type(s)
Heat pump
General heating distribution type(s)
Ducts and registers
Condition of furnace filters
Appeared serviceable
Location for forced air filter(s)
Behind return air grill(s)
Condition of forced air ducts and registers
Appeared serviceable
Condition of cooling system and/or heat pump
Appeared serviceable
Cooling system and/or heat pump fuel type
Electric
Location of heat pump or air conditioning unit
Building exterior
Type
Split system, Heat pump
Estimated age of heat pump or air conditioning unit
2026
Approximate tonnage
2.5
Manufacturer of cooling system and/or heat pump
International comfort product
Heat pump or air conditioner model number
R5H5S30AKAAAABAG
Heat pump or air conditioner serial number
G260916164
Condition of controls
Appeared serviceable
Maintain

The last service date of the forced air heating/cooling system appeared to be within the last year based on information provided to the inspector or labeling on the equipment. If this is true, then routine servicing is not needed at this point. However a qualified HVAC contractor should inspect, clean, and service this system, and make repairs if necessary annually in the future.

Repair/Maintain

Insulation on the heat pump or air conditioning condensing unit's refrigerant lines was deteriorated or missing in some areas. This may result in reduced efficiency and increased energy costs. Recommend that a qualified person replace or install insulation as necessary.

Unit & Information

Bathrooms, Laundry and Sinks

Limitations. The following items are not included in this inspection: overflow drains for tubs and sinks; heated towel racks, saunas, steam generators, clothes washers, clothes dryers. Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of washing machine drain lines, washing machine catch pan drain lines, or clothes dryer exhaust ducts. The inspector does not operate water supply or shut-off valves for sinks, toilets, bidets, clothes washers, etc. due to the possibility of valves leaking or breaking when operated. The inspector does not determine if shower pans or tub and shower enclosures are water tight, or determine the completeness or operability of any gas piping to laundry appliances.

Location #A
Full bath, Master bath
Location #B
Full bath
Location #C
Laundry room/area
Condition of counters
Appeared serviceable
Condition of cabinets
Appeared serviceable
Condition of flooring
Appeared serviceable
Condition of sinks and related plumbing
Required repair, replacement and/or evaluation (see comments below)
GFCI protection
Some present - tested
Condition of toilets
Appeared serviceable
Condition of bathtubs and related plumbing
Required repair, replacement and/or evaluation (see comments below)
Condition of shower(s) and related plumbing
Appeared serviceable
Condition of ventilation systems
Appeared serviceable
Bathroom and laundry ventilation type
with individual ducts
Gas supply for laundry equipment present
No
240 volt receptacle for laundry equipment present
Yes
Repair/Maintain

The sink at location(s) #B drained slowly. Recommend clearing drain and/or having a qualified plumber repair if necessary.

The bathtub at location(s) #B was worn, blemished or deteriorated.

Repair/Replace

One or more bathtub faucet handles at location(s) #A were leaking . Recommend that a qualified person repair or replace handles as necessary.

Faucet handle shield hole was leaking which may indicate a leak in the plumbing system behind the plate.

Interior, Doors and Windows

Limitations. The following items are not included in this inspection: security, intercom and sound systems; communications wiring; central vacuum systems; elevators and stair lifts; cosmetic deficiencies such as Whitfield-pops, scuff marks, dents, dings, blemishes or issues due to normal wear and tear in wall, floor and ceiling surfaces and coverings, or in equipment; deficiencies relating to interior decorating; low voltage and gas lighting systems. Any comments made regarding these items are as a courtesy only. Note that the inspector does not evaluate any areas or items which require moving stored items, furnishings, debris, equipment, floor coverings, insulation or similar materials. The inspector does not test for asbestos, lead, radon, mold, hazardous waste, urea formaldehyde urethane, or any other toxic substance. Some items such as window, drawer, cabinet door or closet door operability are tested on a sampled basis. The client should be aware that paint may obscure wall and ceiling defects, floor coverings may obscure floor defects, and furnishings may obscure wall, floor and floor covering defects. If furnishings were present during the inspection, recommend a full evaluation of walls, floors and ceilings that were previously obscured when possible. Carpeting and flooring, when installed over concrete slabs, may conceal moisture. If dampness wicks through a slab and is hidden by floor coverings that moisture can result in unhygienic conditions, odors or problems that will only be discovered when/if the flooring is removed. Determining the cause and/or source of odors is not within the scope of this inspection.

Condition of exterior entry doors
Required repair, replacement and/or evaluation (see comments below)
Exterior door material
Metal
Condition of interior doors
Appeared serviceable
Condition of windows and skylights
Required repair, replacement and/or evaluation (see comments below)
Type(s) of windows
Metal, Multi-pane, Single-pane, Single-hung
Condition of walls and ceilings
Required repair, replacement and/or evaluation (see comments below)
Wall type or covering
Drywall, Wood
Ceiling type or covering
Drywall, Wood
Condition of flooring
Appeared serviceable
Condition of concrete slab floor(s)
Appeared serviceable
Flooring type or covering
Laminate
Repair/Maintain

Weatherstripping around one or more exterior doors was gapped. Water may enter the building, or energy efficiency may be reduced. Recommend that a qualified person repair or replace weatherstripping as necessary.

Repair/Replace

One or more windows that were designed to open and close were difficult to open and close. Recommend that a qualified person repair windows as necessary so they open and close easily.

Repair/Replace

Glass in one or more windows was cracked, broken and/or missing. Recommend that a qualified contractor replace glass where necessary.

Repair/ReplaceEvaluate

Condensation or staining was visible between multi-pane glass in one or more windows. This usually indicates that the seal between the panes of glass has failed or that the desiccant material that absorbs moisture is saturated. As a result, the view through the window may be obscured, the window's U-value will be reduced, and accumulated condensation may leak into the wall structure below. Recommend that a qualified contractor evaluate and repair windows as necessary. Usually, this means replacing the glass in window frames.

Be aware that evidence of failed seals or desiccant may be more or less visible depending on the temperature, humidity, sunlight, etc. Windows or glass-paneled doors other than those that the inspector identified may also have failed seals and need glass replaced. It is beyond the scope of this inspection to identify every window with failed seals or desiccant.

Maintain

The glazing compound or caulk that holds glass panes in one or more windows was deteriorated and/or substandard. Air and/or water can leak through windows, and wood window frames are prone to rot. This is a conducive condition for wood-destroying organisms. Recommend that a qualified person replace glazing compound as necessary. For more information, visit:
http://www.reporthost.com/?PUTTY

Repair/Replace

Fixtures such as closet shelving were missing. Recommend that a qualified person repair or replace as necessary.

Fireplaces, Stoves, Chimneys and Flues

Limitations. The following items are not included in this inspection: coal stoves, gas logs, chimney flues (except where visible). Any comments made regarding these items are as a courtesy only. Note that the inspector does not determine the adequacy of drafting or sizing in fireplace and stove flues, and also does not determine if prefabricated or zero-clearance fireplaces are installed in accordance with the manufacturer's specifications. The inspector does not perform any evaluations that require a pilot light to be lit, and does not light fires. The inspector provides a basic visual examination of a chimney and any associated wood burning device. The National Fire Protection Association has stated that an in-depth Level 2 chimney inspection should be part of every sale or transfer of property with a wood-burning device. Such an inspection may reveal defects that are not apparent to the home inspector who is a generalist.

Condition of wood-burning fireplaces, stoves
Required repair, replacement and/or evaluation (see comments below)
Wood-burning fireplace type
Masonry with metal liner
Fan or blower installed in wood-burning fireplace or stove
No
Condition of chimneys and flues
Appeared serviceable
Wood-burning chimney type
with metal liner
SafetyRepair/MaintainEvaluate

One or more solid fuel-burning fireplaces or stoves were found at the property. When such devices are used, they should be professionally inspected and cleaned annually to prevent creosote build-up and to determine if repairs are needed. The National Fire Protection Association states that a "Level 2" chimney inspection should be performed with every sale or transfer of property with a wood-burning device. Recommend consulting with the property owner about recent and past servicing and repairs to all wood-burning devices and chimneys or flues at this property. Recommend that a qualified specialist evaluate all solid fuel-burning devices and chimneys, and clean and repair as necessary. Note that if a wood stove insert is installed, it may need to be removed for such an evaluation. For more information, search for "chimney inspection" at:
http://www.reporthost.com/?CSIA

Cornerstone Home Inspectors would like to provide you with the following information to assist you with keeping your home in the best possible working order.

Home appliance estimated design life
1. Gas furnace: 15-20 years
2. Gas boiler: 17-24 years
3. Oil furnace: 18-25 years
4. Electric furnace: 18-25 years
5. Heat pump: 15 years
6. Central air conditioning: 15 years
7. Water heater (tank): 8-12 years
8. Water heater (tankless): 20+ years
9. Range and oven: 18-20 years
10. Refrigerator/Freezer: 18-20 years
11. Dishwasher: 9-11 years
12. Microwave oven: 10 years
13. Range hood and fan: 14 years
14. Food disposal: 10-12 years
15. Garage door opener: 10 years
16. Laundry washing machine: 14 years
17. Laundry dryer: 14 years
18. Bathtub/Sink: 10-30 years
19. Smoke or CO detector: 8-10 years
20. Exhaust fans: 10 years

Home Maintenance Check List

Monthly
1. Clean any removable dishwasher filters.
2. Purge food disposal by filling the kitchen sink with clean water, then turn on the device until the water drains through.
3. Wash refrigerator/freezer interior walls and door gaskets with a solution of one quart of warm water to two tablespoons of baking soda and wipe dry.
4. Vacuum and clean "return" air ducts/grills.
5. Inspect lighting fixtures and replace any burned-out bulbs.
6. Clean clothes dryer lint trap and/or duct for better energy efficiency and to decrease the risk of fire.

Quarterly
1. Inspect and service doors by cleaning and lubricating latches, hinges or replacing weatherstrippings as might be required.
2. Inspect and repair, if necessary, exterior caulking and finish around windows, doors, and siding.
3. Replace/clean, at least quarterly, furnace, heating and cooling system filters.
4. Re-tighten knobs and pulls on cabinets. Clean and lubricate drawer tracks and guides.

Semi-annually
1. Inspect and test smoke and carbon monoxide alarms. Replace backup batteries as might be required.
2. Test (GFCI) ground fault circuit interrupters and (AFCI) arc fault breakers.
3. Inspect and maintain/clean gutters and downspouts. Runoff water must be directed away from the home.
4. Inspect attics and substructure areas for rodent droppings or other signs of pests or leaks/standing water, etc.
5. Prior to the beginning of the rainy season, test sump pumps for adequacy and function.
6. Look for moisture or decay, outside and inside the house, where flat surface decks and landings attach to the home. This is especially important if the landings do not have proper flashings.
7. Clean range hood fan grills and housings.
8. Use a vacuum cleaner to remove dust on coils behind the refrigerator/freezer.

Annually
1. Licensed contractor to inspect and service heating and air conditioning systems.
2. Professional contractor to inspect and service wood-burning appliances and chimneys.
3. Seal any foundation cracks.
4. Inspect, clean and lubricate garage vehicle door tracks and test auto-reverse functions.
5. Clean and lubricate sliding glass door and window tracks.
6. Inspect exterior paint for cracking and wear. Repaint, caulk, and seal as needed.
7. Reseal, as required, wood decks and landings.
8. Inspect, for water damage, pests or rot, any substructure, and attic areas.
9. Inspect roof flashings, chimney caps, shingles.
10. Inspect outside electrical service lines for damage, exposed wires or proximity to tree limbs.
11. Inspect all supply hoses at sinks, toilets and washing machines.
12. Clean and repair caulking or grout in bathrooms or kitchens.
13. Clean bathroom exhaust fan blades and grills.
14. Inspect all electric cords and replace as needed.
15. Change water filters and have freshwater systems professionally serviced.

Tips for keeping drains clear
1. Pour a pot of hot water down the drain once a week to help clear away fat or grease that may have built-up in the drain line or the P-trap.
2. If a drain is clogged, try pouring 1/2 cup of baking soda and 1/2 cup of white vinegar down the drain. Cover the drain and let the mixture sit for a few minutes. Then pour a pot of water down the drain.

General safety tips
Ensure that you know where the following items are located:
1. Emergency contact telephone numbers.
2. Fire extinguishers and water hose pipes.
3. Heating gas/fuel main shutoff valve.
4. Main electrical disconnect circuit breaker(breaker box/service panel).
5. Main drain line clean-out.
6. Main water shut-off valve.
7. All window and door exits.